11.5 Levelling uneven surface
|
|
On the Future of Industrial Floors
by Dipl.-Chem. Dr. Peter Seidler
Industrial Floors 1999, International Colloquium Jan 12-16, 1999 11.5 Levelling uneven surfaces
- Diagnosis and test area
·
tolerances
·
sealing against capillary moisture
·
measuring roughness (e.g. with sand 0.1…0.4 mm)
- Pull-off-strength of > 1.5 N/mm2 from the substrate
- Moisture in the concrete (e.g. CM device)
- Coating must be able to reach zero mm thickness
- Grain size smaller than one third of the thickness
·
multi-layer system if >1 mm thickness
- Ensure adhesion between layers in multi-layer systems
- Temperature must not fall below dewpoint
·
temperature of substrate (°C)
·
air temperature (3°C of substrate)
·
relative humidity (%)
·
draught air (m/sec)
- Flow characteristic influences
·
performance (m2/h/worker)
·
consumption (Ltr/m2/mm)
- Change of amount of filler changes the performance
- Consumption influenced by density (kg/Ltr)
- Imperviousness to liquids only up to a filling ratio 1:6
- Use power float ("helicopter") for a filling ratio 1:14
- GSP (Good Site Practice) as a standard
|